Fiber-reinforced polymer retrofitting of rectangular reinforced concrete columns with or without corrosion

Stathis N. Bousias, Thanasis Triantafillou, Michael N. Fardis, Loukas Spathis, Bill A. O'Regan

    Research output: Contribution to journalArticle

    Abstract

    Twenty concrete columns, with a 250 × 500 mm section and materials and detailing emulating older construction, are tested to investigate, in a systematic way, the effect of important parameters of seismic retrofit with fiber-reinforced polymer (FRP) wraps, as well as the effect of reinforcing bar corrosion on the effectiveness of the retrofitting. As far as the number of FRP layers and the fiber material is concerned, it is concluded that replacing carbon fibers by glass fibers, while maintaining the same extensional stiffness of the FRP jacket in the circumferential direction, leads to about the same performance. Nonetheless, FRP extensional stiffness seems to be the controlling factor up to a certain limit, as increasing the number of carbon fiber-reinforced polymer (CFRP) layers from two to five does not materially improve performance. Previous damage left unrepaired reduces the effectiveness of rehabilitation with FRP wraps. Confinement by the FRP is very effective in increasing concrete strain capacity to levels of 5 to 6% even in the middle of a wide side of the column. Nonetheless, rectangular columns tested in the strong direction (with a 250 mm-wide compression zone) are found to benefit more from FRP wrapping than when tested in their weak direction (with a 500 mm-wide compression zone). Although wrapping with FRP is found to significantly improve seismic performance of columns that suffer from both lack of seismic detailing and of corrosion of the reinforcement, such corrosion materially reduces the effectiveness of FRP wraps as a strengthening measure, as the corroded bars become the weak link of the column, instead of the confined compression zone.

    Original languageEnglish (US)
    Pages (from-to)512-520
    Number of pages9
    JournalACI Structural Journal
    Volume101
    Issue number4
    StatePublished - Jul 1 2004

    Fingerprint

    Retrofitting
    Reinforced concrete
    Polymers
    Corrosion
    Fibers
    Carbon fibers
    Stiffness
    Concretes
    Strengthening (metal)
    Patient rehabilitation
    Glass fibers
    Reinforcement
    Compaction

    Keywords

    • Column
    • Corrosion
    • Fiber-reinforced concrete
    • Polymers
    • Seismic
    • Strength
    • Test

    ASJC Scopus subject areas

    • Building and Construction
    • Civil and Structural Engineering
    • Materials Science(all)

    Cite this

    Fiber-reinforced polymer retrofitting of rectangular reinforced concrete columns with or without corrosion. / Bousias, Stathis N.; Triantafillou, Thanasis; Fardis, Michael N.; Spathis, Loukas; O'Regan, Bill A.

    In: ACI Structural Journal, Vol. 101, No. 4, 01.07.2004, p. 512-520.

    Research output: Contribution to journalArticle

    Bousias, Stathis N. ; Triantafillou, Thanasis ; Fardis, Michael N. ; Spathis, Loukas ; O'Regan, Bill A. / Fiber-reinforced polymer retrofitting of rectangular reinforced concrete columns with or without corrosion. In: ACI Structural Journal. 2004 ; Vol. 101, No. 4. pp. 512-520.
    @article{fa511bb04ae24a1f9011de372bdd49a4,
    title = "Fiber-reinforced polymer retrofitting of rectangular reinforced concrete columns with or without corrosion",
    abstract = "Twenty concrete columns, with a 250 × 500 mm section and materials and detailing emulating older construction, are tested to investigate, in a systematic way, the effect of important parameters of seismic retrofit with fiber-reinforced polymer (FRP) wraps, as well as the effect of reinforcing bar corrosion on the effectiveness of the retrofitting. As far as the number of FRP layers and the fiber material is concerned, it is concluded that replacing carbon fibers by glass fibers, while maintaining the same extensional stiffness of the FRP jacket in the circumferential direction, leads to about the same performance. Nonetheless, FRP extensional stiffness seems to be the controlling factor up to a certain limit, as increasing the number of carbon fiber-reinforced polymer (CFRP) layers from two to five does not materially improve performance. Previous damage left unrepaired reduces the effectiveness of rehabilitation with FRP wraps. Confinement by the FRP is very effective in increasing concrete strain capacity to levels of 5 to 6{\%} even in the middle of a wide side of the column. Nonetheless, rectangular columns tested in the strong direction (with a 250 mm-wide compression zone) are found to benefit more from FRP wrapping than when tested in their weak direction (with a 500 mm-wide compression zone). Although wrapping with FRP is found to significantly improve seismic performance of columns that suffer from both lack of seismic detailing and of corrosion of the reinforcement, such corrosion materially reduces the effectiveness of FRP wraps as a strengthening measure, as the corroded bars become the weak link of the column, instead of the confined compression zone.",
    keywords = "Column, Corrosion, Fiber-reinforced concrete, Polymers, Seismic, Strength, Test",
    author = "Bousias, {Stathis N.} and Thanasis Triantafillou and Fardis, {Michael N.} and Loukas Spathis and O'Regan, {Bill A.}",
    year = "2004",
    month = "7",
    day = "1",
    language = "English (US)",
    volume = "101",
    pages = "512--520",
    journal = "ACI Structural Journal",
    issn = "0889-3241",
    publisher = "American Concrete Institute",
    number = "4",

    }

    TY - JOUR

    T1 - Fiber-reinforced polymer retrofitting of rectangular reinforced concrete columns with or without corrosion

    AU - Bousias, Stathis N.

    AU - Triantafillou, Thanasis

    AU - Fardis, Michael N.

    AU - Spathis, Loukas

    AU - O'Regan, Bill A.

    PY - 2004/7/1

    Y1 - 2004/7/1

    N2 - Twenty concrete columns, with a 250 × 500 mm section and materials and detailing emulating older construction, are tested to investigate, in a systematic way, the effect of important parameters of seismic retrofit with fiber-reinforced polymer (FRP) wraps, as well as the effect of reinforcing bar corrosion on the effectiveness of the retrofitting. As far as the number of FRP layers and the fiber material is concerned, it is concluded that replacing carbon fibers by glass fibers, while maintaining the same extensional stiffness of the FRP jacket in the circumferential direction, leads to about the same performance. Nonetheless, FRP extensional stiffness seems to be the controlling factor up to a certain limit, as increasing the number of carbon fiber-reinforced polymer (CFRP) layers from two to five does not materially improve performance. Previous damage left unrepaired reduces the effectiveness of rehabilitation with FRP wraps. Confinement by the FRP is very effective in increasing concrete strain capacity to levels of 5 to 6% even in the middle of a wide side of the column. Nonetheless, rectangular columns tested in the strong direction (with a 250 mm-wide compression zone) are found to benefit more from FRP wrapping than when tested in their weak direction (with a 500 mm-wide compression zone). Although wrapping with FRP is found to significantly improve seismic performance of columns that suffer from both lack of seismic detailing and of corrosion of the reinforcement, such corrosion materially reduces the effectiveness of FRP wraps as a strengthening measure, as the corroded bars become the weak link of the column, instead of the confined compression zone.

    AB - Twenty concrete columns, with a 250 × 500 mm section and materials and detailing emulating older construction, are tested to investigate, in a systematic way, the effect of important parameters of seismic retrofit with fiber-reinforced polymer (FRP) wraps, as well as the effect of reinforcing bar corrosion on the effectiveness of the retrofitting. As far as the number of FRP layers and the fiber material is concerned, it is concluded that replacing carbon fibers by glass fibers, while maintaining the same extensional stiffness of the FRP jacket in the circumferential direction, leads to about the same performance. Nonetheless, FRP extensional stiffness seems to be the controlling factor up to a certain limit, as increasing the number of carbon fiber-reinforced polymer (CFRP) layers from two to five does not materially improve performance. Previous damage left unrepaired reduces the effectiveness of rehabilitation with FRP wraps. Confinement by the FRP is very effective in increasing concrete strain capacity to levels of 5 to 6% even in the middle of a wide side of the column. Nonetheless, rectangular columns tested in the strong direction (with a 250 mm-wide compression zone) are found to benefit more from FRP wrapping than when tested in their weak direction (with a 500 mm-wide compression zone). Although wrapping with FRP is found to significantly improve seismic performance of columns that suffer from both lack of seismic detailing and of corrosion of the reinforcement, such corrosion materially reduces the effectiveness of FRP wraps as a strengthening measure, as the corroded bars become the weak link of the column, instead of the confined compression zone.

    KW - Column

    KW - Corrosion

    KW - Fiber-reinforced concrete

    KW - Polymers

    KW - Seismic

    KW - Strength

    KW - Test

    UR - http://www.scopus.com/inward/record.url?scp=3242875169&partnerID=8YFLogxK

    UR - http://www.scopus.com/inward/citedby.url?scp=3242875169&partnerID=8YFLogxK

    M3 - Article

    VL - 101

    SP - 512

    EP - 520

    JO - ACI Structural Journal

    JF - ACI Structural Journal

    SN - 0889-3241

    IS - 4

    ER -